Skip to content

АПвП-10 1×120/16 mm² — XLPE medium-voltage cable

АПвП-10 1×120/16 mm² — medium-voltage single-core power cable with an aluminium conductor, XLPE insulation, copper screen and polyethylene outer sheath. This is the АПвП construction, not АПвЭгП. Longitudinal water-blocking is not claimed for the АПвП designation without a confirmed datasheet.

Cable designation АПвП-10 1×120/16
Voltage class 10 kV
Construction Single-core power cable
Conductor material Aluminium
Nominal conductor cross-section 120 mm²
Copper screen cross-section (designation) 16 mm²
Insulation Cross-linked polyethylene (XLPE)
Outer sheath Polyethylene (PE)
Nominal frequency 50 Hz
Maximum continuous conductor temperature +90 °C
Conductor temperature in short circuit (reference maximum) +250 °C
Operating ambient temperature (reference) −60 … +50 °C
Minimum laying temperature without preheating (reference) −20 °C
Minimum bending radius for single-core cable (reference) 15× cable outer diameter
Laying In ground with mechanical protection; in air with additional fire-protection measures
Manufacturer To be confirmed before supply

Important: Operating figures above are general reference limits for АПвП 10–35 kV as published in technical literature and must be verified against the actual supplying manufacturer's datasheet. Outer diameter, mass, ampacity, certification and reel length are not confirmed.

Technical reference (not a VIKAB product passport): АПвП / ПвП medium-voltage cable construction.

Request a quote via WhatsApp

Technical reference – manufacturer catalogue

Cable designation АПвП-10 1×120/16
Rated voltage 10 kV
Aluminium conductor 120 mm²
Copper screen 16 mm²
Max. continuous conductor temperature +90 °C
Emergency conductor temperature (reference) +130 °C
Short-circuit conductor temperature (reference) +250 °C
Calculated outer diameter (Elektrokabel reference) 30.2 mm
Calculated cable weight (Elektrokabel reference) 957 kg/km

The dimensional values above, where present, come from Elektrokabel Kolchuginsky manufacturer's general XLPE 10–35 kV catalogue (p. 62), and are not a product-specific ICG Supply certificate. The exact producer, manufacturing standard, certifications, measured dimensions and rated ampacity for the supplied batch must be confirmed before order. The reference images represent the general cable construction, not exact cross-sectional dimensions.

Open technical source catalogue (PDF)

Price on request

Stock, price and lead time are confirmed upon inquiry. Please specify quantity in metres.

Request a quote on WhatsApp