Skip to content

N2XH / NHXMH — halogen-free copper cables

Cable selection for power circuits and fixed installation

CuCopper conductors
HFHalogen-free sheath
mm²Type and cross-section selection

Products in our catalogue

NHXMH

Type and size, mm²SupplierAvailabilityRequest price
NHXMH 2×1.5ICG SupplyCheck availabilityRequest price
NHXMH-J 2×2.5ICG SupplyCheck availabilityRequest price
NHXMH-J 2×4ICG SupplyCheck availabilityRequest price
NHXMH-O 2×6ICG SupplyCheck availabilityRequest price

NHXMH technical data

Data from existing NHXMH product records. N2XH specifications are confirmed for the selected construction.

Type and sizeRated voltage, kVInsulation thickness, mmCurrent in air, ACurrent in ground, AMin. bending radius, mmOutside diameter, mmWeight, kg/km
NHXMH 2×1.50.660.5253134.88.7120
NHXMH-J 2×2.50.660.53440389.5150
NHXMH-J 2×40.660.6455243.610.9210
NHXMH-O 2×60.660.6566447.611.9270

Operating temperature: −50 … +50 °C. Current ratings come from the product records. Permissible current depends on installation conditions and must be checked for your project.

N2XH technical specifications — reference data

Reference values from the YUZHCABLE N2XH catalogue. Actual cable construction and manufacturer must be confirmed for supplied goods. The correspondence of products labelled N2XH-1 also requires verification.

Cores × cross-section, mm²Insulation, mmOuter Ø, mm (approx.)Mass, kg/km (approx.)Resistance at 20°C, Ω/kmCurrent in air, ACurrent buried, A*
N2XH 2×1.5 0.71212012.12531
N2XH 2×2.5 0.7121507.413440
N2XH 2×4 0.7131904.614552
N2XH 2×6 0.7142903.085664
N2XH 2×10 0.7153801.837886
N2XH 2×16 0.7165501.15104112
N2XH 2×25 0.9188400.727141144
N2XH 3×1.5 0.71214012.12531
N2XH 3×2.5 0.7131807.413440
N2XH 3×4 0.7142304.614552
N2XH 3×6 0.7153203.085664
N2XH 3×25 0.92110800.727141144
N2XH 4×1.5 0.71217012.12328
N2XH 4×2.5 0.7132207.413137
N2XH 4×4 0.7152904.614148
N2XH 4×6 0.7163903.085259
N2XH 4×10 0.7185901.837279
N2XH 4×16 0.7218601.1596104
N2XH 4×25 0.92513600.727131133
N2XH 5×1.5 0.71319012.12328
N2XH 5×2.5 0.7142507.413137
N2XH 5×4 0.7163404.614148
N2XH 5×6 0.7174703.085259
N2XH 5×10 0.7207201.837279
N2XH 5×16 0.72310501.1596104
N2XH 5×25 0.92515800.727131133
N2XH-1 1×16 0.792201.15139175
N2XH-1 1×25 0.9113300.727188228
N2XH-1 1×35 0.9124300.524230274
N2XH-1 1×50 1.0135600.387281325
N2XH-1 1×70 1.1157800.268356399
N2XH-1 1×95 1.11710400.193440478
N2XH-1 1×120 1.21813000.153514546
N2XH-1 1×150 1.42115800.124591614
N2XH-1 1×185 1.62319600.0991685695
N2XH-1 1×240 1.72425100.0754821812
N2XH-1 3×16/10 0.7/0.7197701.15/1.83104112
N2XH-1 3×25/16 0.9/0.72211700.727/1.15141144
N2XH-1 3×35/16 0.9/0.72414800.524/1.15172173
N2XH-1 3×50/25 1.0/0.92820300.387/0.727209205
N2XH-1 3×70/35 1.1/0.93228000.268/0.524265253
N2XH-1 3×95/50 1.1/1.03637600.193/0.387327304
N2XH-1 3×120/70 1.2/1.14148300.153/0.268381347
N2XH-1 3×150/70 1.4/1.14456500.124/0.268437391
N2XH-1 3×185/95 1.6/1.14870500.0991/0.193504442
N2XH-1 3×240/120 1.7/1.25693300.0754/0.153598515

Rating conditions: air +25°C; soil +15°C, burial depth 0.7 m, thermal resistivity 1.2 K·m/W. Single-core figures are for d.c.; a.c. rating depends on laying configuration. Underground installation requires mechanical protection in a duct or conduit. *Verify actual laying conditions before engineering use.

YUZHCABLE · N2XH · Cables, Wires, Cords and Conductors, pp. 60–63 · HD 604 / HD 627 / IEC 60502-1 · 0.6/1 kV.

Compare products

Select 2 or 3 items to compare

Select first item to compare

Select second item to compare

Select third item to compare

Compare